Conductivity transmitter
16 variants, (0)4…20mA or 0…5(10)V output
- For connecting the conductivity sensors LM and LMN
- 8 variants with adjustable measuring range 0…100mS:
- 0…20mA, 4…20mA, 0…5V or 0…10V output
- 12V or 24V DC operating voltage
- 8 further variants with extended measuring range up to 1000mS
- automatic temperature compensation
- galvanic isolation
- in a practical DIN-rail housing
- Made in Germany
ab €198.00 net
Function
The device converts the conductivity of the measuring solution into a low-impedance output signal of 0(4)…20mA or 0…5/10V.
Input and output are galvanically isolated. Fluctuating temperatures of the medium are compensated by automatic temperature compensation.
Advantages
Fully analogue:
The transmitters are equipped exclusively with analogue components. There is no falsification of the measurement results due to analogue/digital conversion.
Pin assignment
Connection diagram
Temperature compensation
Zur Temperature compensation a 2 kOhm fixed resistor or an NTC temperature sensor is required. The fixed resistor is connected to the transmitter ex works.
Leave the fixed resistor on the device if the measurement takes place at an average temperature of approx. 25°C. In this case, no NTC is required.
If the temperature of the measuring solution deviates significantly (>10°C) from an average temperature of 25°C, an NTC must be used for temperature compensation.
Use a measuring cell of type LMN with NTC.
Remove the fixed resistor and connect the NTC to terminals 5+6.
Note:
Terminals 5+6 must always be connected: connect either a fixed resistor or an NTC.
Setting the measuring range
Use the jumpers to set the measuring range and adapt the transmitter to the cell constant of the conductivity sensor used.
| Cell constant of the conductivity sensor | Jumper 20mS | Jumper 2mS | Jumper 200µS |
|---|---|---|---|
| ZK=5: | 100mS | ||
| ZK=1: | 20mS | 2mS | 200.0µS |
| ZK=0.1: | 200µS | 20µS | |
| ZK=0.01: | 20µS | 2µS |
The jumpers and potentiometers are accessible after opening the housing cover.
![]() |
With very long cables to the sensor, you can correct the calibration using the potentiometers. However, this requires a reference solution. Please contact us.
Technical data
| Measuring range (adjustable via jumper): |
| ||||||||||
| Extended measuring range (fixed, not adjustable): | The special versions item no. 1000-0022-0410-09 to -16 have an extended measuring range:
| ||||||||||
| Conductivity sensor: | All sensors of type LM and LMN with NTC for automatic temperature compensation | ||||||||||
| Output: | 0…20mA, 4…20mA, 0…5V or 0…10V according to the type plate | ||||||||||
| Accuracy, linearity [% of full scale]: | ±1 ±2 at 20mS ±5 at 200mS | ||||||||||
| Input resistance [ohm]: | 1012 | ||||||||||
| Temperature compensation: | NTC or fixed resistor 2 kOhm approx. 2.2%/°C natural waters | ||||||||||
| Reference temperature [°C]: | 25 | ||||||||||
| Operating voltage [V]: | 12V DC or 24V DC opt. (±10%, regulated) according to the type plate. It is essential to use a regulated supply voltage. | ||||||||||
| Ambient temperature [°C]: | 0…60 | ||||||||||
| Degree of protection: | IP 20 | ||||||||||
| Current consumption [mA]: | max. 50 | ||||||||||
| Dimensions, H x W x D [mm]: | 75 x 60 x 30 | ||||||||||
| Weight [g]: | 70 |
Items & prices
| Art.-Nr. | Description | Net price | Order / enquire |
|---|---|---|---|
| 1-0022-0410-1 | Output: 4 - 20mA, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-2 | Output: 0 - 20mA, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-3 | Output: 4 - 20mA, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-4 | Output: 0 - 20mA, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-5 | Output: 0 - 5V, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-6 | Output: 0 - 10V, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-7 | Output: 0 - 5V, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-8 | Output: 0 - 10V, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNAdjustable measuring range: 2µS…100mS | €198.00 | |
| 1-0022-0410-9 | Output: 4 - 20mA, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 | |
| 1-0022-0410-10 | Output: 0-20mA, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 | |
| 1-0022-0410-11 | Output: 4 - 20mA, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 | |
| 1-0022-0410-12 | Output: 0 - 20mA, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 | |
| 1-0022-0410-13 | Output: 0 - 5V, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 | |
| 1-0022-0410-14 | Output: 0 - 10V, supply voltage: 24V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 | |
| 1-0022-0410-15 | Output: 0 - 5V, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 | |
| 1-0022-0410-16 | Output: 0 - 10V, supply voltage: 12V DCConductivity transmitter with galvanic isolationInput: conductivity sensor LM or LMNFixed measuring range: 200mS at ZK=1 and 1000mS at ZK=5 | €198.00 |