LMA-I
Conductivity meter with integrated electronics
- Conductivity meter with two analogue outputs 0(4)…20mA
- programmable measuring range
- conductive measurement of specific electrical conductivity in liquids
- Temperature measurement 0…100°C with Pt1000
- Made in Germany
ab €30.00 net
Description
Electrolytic conductivity is, alongside the pH value, the most important parameter in chemical process analysis.
It is a measure of the ability of an aqueous solution to conduct electric current. All processes in which salts, acids and bases play a role can thus be monitored, controlled or regulated by measurement.
The conductivity meters of the LMA-I series have a programmable measuring range and two analogue outputs in a compact housing.
Application
From water treatment to industrial process water with high demands in terms of temperature, pressure, tolerance of contamination and chemical resistance.
Outputs
One analogue output 0(4)…20mA is assigned to conductivity, the other analogue output to temperature.
The conductivity measuring range is programmed ex works according to customer specifications; please download the configuration software, make the settings and export a configuration file. Please supply this file with your order.
Alternatively, you can set the values with the configuration software and load them onto the device on site using the configuration cable.
Dimensions
Pin assignment
![]() |
|
Note:
Recommended connection: 0.25…0.34mm²; strip 10mm of stranded wire and tin.
Technical data
| Measuring surfaces: | ZK0.01: stainless steel 1.4404 ZK1, ZK0.1: graphite |
| Cell shaft: | PP / PVDF (optional) |
| Materials in contact with the medium: | ZK 0.01, ZK0.1: stainless steel 1.4404 and EPDM ZK1: titanium, graphite, EPDM |
| Screw-in thread: | 3/4" |
| Programmable measuring ranges: | ZK1: from 0…100µS to 0…200mS in 11 steps ZK0.1: from 0…10µS to 0…1mS in 7 steps ZK0.01: from 0…100nS to 0…100µS in 10 steps |
| Measuring accuracy: | ±3% of reading |
| Temperature measuring range [°C]: | 0…100, Pt1000 Kl. B1 |
| Temperature resistance of measuring cells: | 0…60°C (PP) 0…110°C (PVDF) |
| Pressure resistance: | 16 bar up to 60°C (PP) 16 bar up to 110°C (PVDF) |
| Degree of protection: | IP 65 |
| Temperature compensation: | lin. 0…6%/°C nat. 2.2%/°C |
| Reference temperature [°C]: | 20/25 |
| Galvanic isolation of measuring input: | Ja |
| Analogue output: | 2x 0(4)…20mA |
| Ambient temperature [°C]: | -20…50 |
| Operating voltage [V]: | 24V DC ±10% also available with 12V DC on request |
| Current consumption [mA]: | <50mA |
| Cable connection: | 6x0.25mm² |
Downloads
- Data sheet
- Configuration software LMA and the SHA 256 signature for verification
- Software operating manual
Items & prices
| Art.-Nr. | Description | Net price | Order / enquire |
|---|---|---|---|
| 1-0022-8020-1 | LMA-I ZK1Cell shaft made of PPProgrammable from 100µS to 200ms2x 0(4)…20mA for conductivity and temperatureScrew-in thread: 3/4"Measuring input galvanically isolated | €306.00 | |
| 1-0022-8025-1 | LMA-I ZK1Cell shaft made of PVDFProgrammable from 100µS to 200ms2x 0(4)…20mA for conductivity and temperatureScrew-in thread: 3/4"Measuring input galvanically isolated | €346.00 | |
| 1-0022-8020-01 | LMA-I ZK01Cell shaft made of PPProgrammable from 10µS to 1ms2x 0(4)…20mA for conductivity and temperatureScrew-in thread: 3/4"Measuring input galvanically isolated | €286.00 | |
| 1-0022-8025-01 | LMA-I ZK01Cell shaft made of PVDFProgrammable from 10µS to 1ms2x 0(4)…20mA for conductivity and temperatureScrew-in thread: 3/4"Measuring input galvanically isolated | €326.00 | |
| 1-0022-8020-001 | LMA-I ZK001Cell shaft made of PPProgrammable from 100nS to 100µS2x 0(4)…20mA for conductivity and temperatureScrew-in thread: 3/4"Measuring input galvanically isolated | €306.00 | |
| 1-0022-8025-001 | LMA-I ZK001Cell shaft made of PVDFProgrammable from 100nS to 100µS2x 0(4)…20mA for conductivity and temperatureScrew-in thread: 3/4"Measuring input galvanically isolated | €346.00 | |
| 1-0022-8090 | Configuration cable with PC software for LMA series | €56.00 | |
| 1-0022-8083 | M12-GX12, 3mConnection cable for LMA3m, 5-pole x 0.25 mm², PVC cable, shielded, degree of protection IP 67 | €30.00 | |
| 1-0022-8086 | M12-GX12, 6mConnection cable for LMA6m, 5-pole x 0.25 mm², PVC cable, shielded, degree of protection IP 67 | €42.00 |
All prices in euros net plus statutory VAT and shipping costs. Errors and changes excepted. Our terms and conditions apply: AGB.