SMART 96-2 pH + redox
230V AC or 9…36V DC
- for displaying pH, redox and temperature
- 2 analogue outputs
- 3 potential-free relay outputs, configurable as LS, alarm, PPL, PPF
- Illuminated display
- in DIN housing 96x48 for control cabinet installation
- waterproof front IP 65
- 2 variants:
- 230 V AC or
- 9…36 V DC operating voltage
- Made in Germany
ab €441.00 net
Suitable pH and redox sensors
Measuring inputs
pH / redox:
| Measuring range [pH / redox]: | 0.00…14.00 pH / ±1200 mV |
| Accuracy: | ±0.02pH / 2mV |
| Input resistance [ohm]: | >1012 |
| Special features: |
|
Temperature:
| Measuring range [°C]: | -20…110 |
| Accuracy [°C]: | 0.5 |
| Sensor: | Pt100 in 2- or 3-wire technology |
| Miscellaneous: | Cable break / short-circuit detection |
3 relay outputs
| Configuration: | 3 potential-free relay contacts (changeover) 250 V AC / 8 A with resistive load, freely assignable to the measuring inputs. Configurable as: |
| GW: | Limit switch |
| Alarm: | Monitoring |
| PRI: | proportional pulse length controller |
| PRF: | proportional pulse frequency controller |
LS: limit switch adjustable
| Possible switching characteristics: | NC / NO |
| Maintained or momentary contact | Selectable |
| Switching delay [sec.]: | 0…9999 |
| Switching hysteresis: | 0…800 digits |
Alarm: monitoring adjustable
| Signal types: | visual or acoustic signal |
| Time delay: | 0.1…30 min. |
PPL: proportional pulse length controller
| Integral component: | can be activated in 3 stages |
| Period [sec]: | 4…120 |
PPF: proportional pulse frequency controller
| Integral component: | can be activated in 3 stages |
| Pulse repetition frequency [Hz]: | 0…3 |
| Pulse length [ms]: | 170 |
2 analogue outputs
| Standard signal [mA]: | 0(4)…20, freely assignable to the display value 0…5V/10V by connecting a 250/500 ohm resistor in parallel |
| Maximum load: | 500 Ohm |
| Galvanic isolation from measuring input: | Yes |
Rear panel
General technical data
| Operating voltage [V AC]: | 85…264V, 50/60 Hz or 9…36 VDC |
| Power consumption [VA]: | < 5 |
| Ambient temperature [°C]: | 0…50 |
| Housing: | Panel-mount housing according to DIN 43 700 |
| Material: | flame-retardant Noryl |
| Front dimensions [mm]: | 48 x 96 |
| Panel cut-out [mm]: | 44.0 x 90.5 |
| Installation depth [mm]: | 120 |
| Connections: | Plug-in screw terminals |
| Weight [g]: | ca. 350 |
| Climatic resistance: | rel. humidity =< 75% without condensation |
| Electrical safety: | according to EN 61 010 Clearances and creepage distances for -overvoltage category II -pollution degree 2 |
| Protection class: | 1 |
| Degree of protection: | according to EN 60 529, front IP65 |
| Electromagnetic compatibility: | according to NAMUR recommendation NE21, EN 50 081 part 1, EN 50 082 part 2 |
Downloads
Items & prices
| Art.-Nr. | Description | Net price | Order / enquire |
|---|---|---|---|
| 1-1300-0301 | SMART 96-2 pH+redox+temperatureµP measuring and control unit for pH/redox + temp.3 potential-free relay outputs configurable as LV, alarm, PLC, PFC2 analogue outputs 0(4)...20mAMains: 85...264 V 50/60 HzDimensions: DIN housing 96x48mm for control cabinet installationDegree of protection IP65 | €441.00 | |
| 1-1300-0301DC | SMART 96-2 pH+redox+temperature 9…36VDCµP measuring and control unit for pH/redox + temp.3 potential-free relay outputs configurable as LV, alarm, PLC, PFC2 analogue outputs 0(4)...20mAMains: 9...36VDCDimensions: DIN housing 96x48mm for control cabinet installationDegree of protection IP65 | €441.00 |
All prices in euros net plus statutory VAT and shipping costs. Errors and changes excepted. Our terms and conditions apply: AGB.