Albert-Einstein-Straße 1, 49076 Osnabrück, Germany +49 541 959 88 44 0 info@imp24.de
imp ingenieurgesellschaft mbh Request list
SMART 96-2 conductivity + temperature 230V AC or 9…36V DC

SMART indicators and controllers

SMART 96-2 conductivity + temperature

230V AC or 9…36V DC

  • for displaying conductivity and temperature
  • 2 analogue outputs 0(4)…20mA
  • 3 potential-free relay outputs, configurable as LS, alarm, PPL, PPF
  • Illuminated display
  • in DIN housing 96x48 for control cabinet installation
  • waterproof front IP 65
  • 2 variants:
    • 230 V AC or
    • 9…36 V DC operating voltage
  • Made in Germany

ab €441.00 net

Suitable conductivity sensors
  • 2-electrode sensors, type LM
  • 2-electrode sensors with Pt100 for temperature compensation, type LMP
  • 4-electrode sensors with Pt100 for temperature compensation, type LMPx-4E-PP
Measuring ranges

The instrument can be set to S/cm or ohms.

Sensor Measuring range
LMP1-4E-PP: 200mS
LMP5-4E-PP: 800mS
LM-5 od. LMP-5: 999.9mS
LM-1 od. LMP-1: 9999µS / 99.99mS / 210mS
999.9µS / 9999µS / 99.99mS
LM-0.1 od. LMP-0.1: 99.99µS / 999.9µS / 9999µS
LM-0.01 od. LMP-0.01: 9.999µS / 99.99µS / 999.9µS
Measuring inputs
Conductivity:
Parameter Value
ZK: adjustable, 0.0025 - 50.000
Accuracy: ± 1.5% or 10 digits
Sensor: conductive 2-/4-electrode measuring cell
TK: 2.2% natural waters / 0-6.9% linear
Special features:
  • Automatic temperature compensation via Pt100
  • Measuring input galvanically isolated from the instrument
Temperature:
Measuring range [°C]: -20…110
Accuracy [°C]: 0.5
Sensor: Pt100 in 2- or 3-wire technology
Miscellaneous: Cable break / short-circuit detection
3 relay outputs
Configuration: 3 potential-free relay contacts (changeover)
250 V AC / 8 A with resistive load, freely assignable to the measuring inputs.
Configurable as:
GW: Limit switch
Alarm: Monitoring
PRI: proportional pulse length controller
PRF: proportional pulse frequency controller
LS: limit switch adjustable
Possible switching characteristics: NC / NO
Maintained or momentary contact Selectable
Switching delay [sec.]: 0…9999
Switching hysteresis: 0…800 digits
Alarm: monitoring adjustable
Signal types: visual or acoustic signal
Time delay: 0.1…30 min.
PPL: proportional pulse length controller
Integral component: can be activated in 3 stages
Period [sec]: 4…120
PPF: proportional pulse frequency controller
Integral component: can be activated in 3 stages
Pulse repetition frequency [Hz]: 0…3
Pulse length [ms]: 170
2 analogue outputs
Standard signal [mA]: 0(4)…20, freely assignable to the display value
0…5V/10V by connecting a 250/500 ohm resistor in parallel
Maximum load: 500 Ohm
Galvanic isolation from measuring input: Yes
Rear panel
Pin assignment
General technical data
Operating voltage [V AC]: 85…264V, 50/60 Hz or
9…36 VDC
Power consumption [VA]: < 5
Ambient temperature [°C]: 0…50
Housing: Panel-mount housing according to DIN 43 700
Material: flame-retardant Noryl
Front dimensions [mm]: 48 x 96
Panel cut-out [mm]: 44.0 x 90.5
Installation depth [mm]: 120
Connections: Plug-in screw terminals
Weight [g]: ca. 350
Climatic resistance: rel. humidity =< 75% without condensation
Electrical safety: according to EN 61 010
Clearances and creepage distances for
-overvoltage category II
-pollution degree 2
Protection class: 1
Degree of protection: according to EN 60 529, front IP65
Electromagnetic compatibility: according to NAMUR recommendation NE21, EN 50 081 part 1, EN 50 082 part 2
Downloads

Items & prices

Art.-Nr.DescriptionNet priceOrder / enquire
1-1300-0401SMART 96-2 conductivity + temperatureµP conductivity measuring and display unit for passiveconductivity cells LM, LMP3 potential-free relay outputs configurable as LV, alarm, PLC, PFC2 analogue outputs 0(4)...20mAMains: 85...264 V 50/60 HzDimensions: DIN housing 96x48mm for control cabinet installation€441.00
1-1300-0401DCSMART 96-2 conductivity + temperature 9…36VDCµP conductivity measuring and display unit for passiveconductivity cells LM, LMP3 potential-free relay outputs configurable as LV, alarm, PLC, PFC2 analogue outputs 0(4)...20mAMains: 9...36VDCDimensions: DIN housing 96x48mm for control cabinet installation€441.00

All prices in euros net plus statutory VAT and shipping costs. Errors and changes excepted. Our terms and conditions apply: AGB.