FAQ: Ampere-hour meters
What must be considered when dimensioning the shunt resistor?
When dimensioning the measuring input of the ampere-hour meter, the shunt data are of decisive importance. These are e.g. 60mV / 120A.
Both values must be specified when ordering! The shunt value and the rectifier rating are usually different, with the shunt value slightly higher to avoid operation at the upper limit. Nevertheless, it is the shunt value that is relevant for configuring the AZ x000 and not(!) the rectifier rating! Furthermore, only the current is decisive for dimensioning the shunt size!
How many rectifiers can be connected to the meter when recording total currents?
In principle, there is no limit.
However, one potential isolation module must be used per rectifier. Furthermore, the instrument must be designed for the max. total current.
Can the AZ4000 also be used as a metal weight counter (e.g. for silver)?
The AZ4000 has all the functions required to be used as a metal weight counter for silver. For this purpose, the metal equivalent (e.g. 4.02 g/Ah) is permanently stored during adjustment. The AZ 4000 has a preset counter, counting either up or down, and an up-counting totaliser. When the preset value adjustable on the front of the instrument (also in grams) is reached, a potential-free relay switches. When ordering, the input signal must be clearly known and the exact metal equivalent specified. Please also state whether the preset counter should count up or down.
How do I reset the totaliser on the AZ4000?
The totaliser is reset as follows:
- fold out the supplied key so that the metal blade is visible
- insert the key below the totaliser button
- press the key including the button in with increased pressure
- The reset takes place automatically at the moment of pressing!
Is the dosing interval selectable on the AZ x000 DSZ?
No. The dosing interval is factory-set to 100 Ah but can be supplied differently on request, e.g. with 10 Ah. When the dosing interval is reached, the dosing output is activated for the time set in the dosing timer (0-99 sec.).
How do I convert the shunt data into the number of pulses?
With a current of 50 A, an ampere-hour meter gives 50 pulses per hour, an ampere-minute meter 50 pulses per minute. An ampere-hour meter should therefore be used with one decimal place, which then gives 500 pulses per hour or 12 pulses/min.
With a current of 1000 A, an ampere-hour meter gives 1000 pulses per hour or 17 pulses per minute. The ampere-hour meter should therefore be used without a decimal place. With a current of this magnitude, an ampere-minute meter makes no sense.